Application |
Measuring element |
ceramic-capacitive pressure measuring cell |
Application |
for industrial applications |
Media |
liquids and gases |
Medium temperature [°C] |
-25...80 |
Pressure rating |
|
Min. bursting pressure |
|
Vacuum resistance [mbar] |
-1000 |
Type of pressure |
relative pressure |
MAWP (for applications according to CRN) |
|
Electrical data |
Operating voltage [V] |
18...30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] |
< 35 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
0.3 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250 |
Switching frequency DC [Hz] |
< 500 |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20; (scalable 1:5) |
Max. load [Ω] |
500 |
Analogue voltage output [V] |
0...10; (scalable 1:5) |
Min. load resistance [Ω] |
2000 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Measuring range |
-14.5...362.5 psi |
-1...25 bar |
-0.1...2.5 MPa |
|
Set point SP |
-12...362.5 psi |
-0.85...25 bar |
-0.085...2.5 MPa |
|
Reset point rP |
-13.5...361 psi |
-0.95...24.9 bar |
-0.095...2.49 MPa |
|
Analogue start point |
-14.5...290 psi |
-1...20 bar |
-0.1...2 MPa |
|
Analogue end point |
58...362.5 psi |
4...25 bar |
0.4...2.5 MPa |
|
In steps of |
0.5 psi |
0.05 bar |
0.005 MPa |
|
Accuracy / deviations |
Switch point accuracy [% of the span] |
< ± 0,4; (Turn down 1:1) |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] |
< ± 0,1; (Turn down 1:1) |
Long-term stability [% of the span] |
< ± 0,05; (Turn down 1:1; per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] |
0,2; (-25...80 °C) |
Temperature coefficient span [% of the span / 10 K] |
0,2; (-25...80 °C) |
Response times |
Response time [ms] |
< 1.5 |
Delay time programmable dS, dr [s] |
0...50 |
Damping for the switching output dAP [s] |
0...4 |
Damping for the analogue output dAA [s] |
0...4 |
Max. response time analogue output [ms] |
3 |
Software / programming |
Parameter setting options |
hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Interfaces |
Communication interface |
IO-Link |
Transmission type |
COM2 |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
IO-Link device ID |
472 d / 00 01 d8 h |
Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode |
yes |
Required master port type |
A |
Process data analogue |
1 |
Process data binary |
2 |
Min. process cycle time [ms] |
2.3 |
Operating conditions |
Ambient temperature [°C] |
-25...80 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 65; IP 67 |
Tests / approvals |
EMC |
DIN EN 61000-6-2 |
|
DIN EN 61000-6-3 |
|
|
Shock resistance |
DIN EN 60068-2-27 |
50 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 |
20 g (10...2000 Hz) |
|
MTTF [years] |
138 |
UL approval |
|
Pressure Equipment Directive |
Sound Engineering Practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data |
Weight [g] |
243.8 |
Materials |
stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) |
stainless steel (1.4404 / 316L); AI2O3 (96 %; ceramics); FKM |
Min. pressure cycles |
100 million |
Tightening torque [Nm] |
> 50; (depends on lubrication, seal and pressure rating) |
Process connection |
threaded connection 1/4 NPT external thread |
Restrictor element integrated |
no (can be retrofitted) |
Displays / operating elements |
Display |
Display unit |
3 x LED, green (bar, psi, MPa) |
switching status |
2 x LED, yellow |
measured values |
alphanumeric display, red/green 4-digit |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12; Contacts: gold-plated |